Arlington's Cableway(TM) Cable Runway Support System
UL Listed as a cable runway support system, up to 6 lbs per linear foot
Communications Cable
Capacity
60 Cat 6 Communications Cables,
or equivalent volume of other communications cables
Power Conductor Fill
Capacity: 40 Units, As shown below
NM Cable with
Copper Conductors |
Fill Units
per Cable |
(or) Total Cables
of One Size |
|
14/2 |
1 ea. |
40 |
|
14/3 |
1.25 ea. |
32 |
|
14/4 |
1.5 ea. |
26 |
|
12/2 |
1.5 ea. |
26 |
|
12/3 |
1.75 ea. |
22 |
|
12/4 |
2 ea. |
20 |
|
10/2 |
2 ea. |
20 |
|
10/3 |
2.25 ea. |
17 |
|
8/2 |
2.25 ea. |
17 |
|
8/3 |
2.5 ea. |
16 |
|
6/2 |
2.75 ea. |
14 |
|
6/3 |
3 ea. |
13 |
|
Example:
| (19) |
14/2 @ 1 |
= 19 units |
| (8) |
12/2 @1.5 |
= 12 units |
| (4) |
10/3 @2.25 |
= 9 units |
| |
Total |